Hager HMB180 single-pole MCB rated 80A with B-curve characteristic and 15kA short-circuit breaking capacity to IEC 60898-1. Mounts straight onto DIN rail.

  • Rated 80A at 30°C, derated at higher temperatures
  • 15kA Icn at 230V AC (IEC 60898-1)
  • 240–415V AC, 50–60 Hz
  • Operating range: −25°C to 70°C
  • Screw terminals: accepts 1–70 mm² rigid or 1–50 mm² flexible copper
Specifications

Poles

1P

Current Rating

80A

Trip Curve

B

Voltage

240–415V AC

Frequency

50–60 Hz

Breaking Capacity (Icn)

15kA (230V AC, IEC 60898-1)

Service Breaking Capacity (Ics)

7.5kA AC (IEC 60898-1)

Insulation Voltage

500V

Impulse Withstand Voltage

6000V

Terminal Type

Screw terminal (top and bottom)

Cable Range

1–70 mm² rigid, 1–50 mm² flexible

Operating Temperature

−25°C to 70°C

IP Rating

IP20

Module Width

1.5 modules (27mm)

Mechanical Endurance

20,000 cycles

Electrical Endurance

4,000 cycles